e bannerespaEΤΠΑ460X60
English (UK)
Fuse-Cutout Disconnecting Switches

Medium Voltage Fuse Cut-out Disconnecting Switches, operating at maximum Voltage 24 kV.

They are assembled in three versions:

  • Normal Insulation with porcelain insulators.
  • Heavy Insulation with porcelain insulators.
  • Heavy Insulation with HTV silicon rubber insulators.
Description

This single venting type cutout fuses provide a full-fault spectrum protection of 24kV overhead distribution systems whether applied to overhead transformers, capacitors, cables or lines.

'Full fault spectrum protection' means that cutouts interrupt all faults from the lowest current, that will melt the fuse link, to the maximum rated interrupting current, under all realistic transient recovery voltage conditions.

Fuse cutouts employ a single venting 'down and away only', a recovery important feature where exhaust must be kept out of other phases in overbuilt circuits.

Operating Conditions

Ambient Temperatures

 

-150C to +450C

Max. Altitude

 

1.000 m

Relative Humidity

 

≤ 95 %

Max. Ice Coating

 

10 mm

Pollution Level

 

Moderate to Heavy

Wind Speed

 

150 km/h

Insulation Levels

 

 

Normal Insulation

 

Heavy Insulation

 

HTV Silicon Heavy Insulation

Type

LN

LH

LSH

Creepage Distance

400 mm

530 mm

530 mm

Material

Porcelaine

Porcelaine

HTV Silicone Rubber

Net Weight

10 kg

10,5 kg

5 kg

 

Properties

Nominal Voltage

 

20 kV

Max. Operating Voltage

 

24 kV

Nominal Frequency

 

50 Hz

Nominal Current

 

100 A

Short Circuit Level

 

250 MVA

Interrupting Current

 

7,2 kA

Power Frequency Withstand Voltage (dry)

 

60 kV

Power Frequency Withstand Voltage (wet)

 

60 kV

Lightning Impulse Withstand Voltage (BIL)

 

125 kV

Impulse Withstand Voltage 1,2/50μsec

 

125 kV

The Disconnectors are manufactured to comply to the same Electrical Characteristics regardless the insulator type.

Type test reports

Our products have sucessfully been type tested and have been awarded the relevant type test certificates.

 fusecutouttypetestreport1     fusecutouttypetestreport2

 

 

fusecutouttypetestreport3        fusecutouttypetestreport4

PPC Product Codes

LN (Normal Insulation) Base

431000098

LH (Heavy Insulation) Base

431000096

LN Fuse Case

430000099

LH Fuse Case

430000097

Rapid Melting Fuse Link 3A (3K)

441003389

Rapid Melting Fuse Link 6A (6K)

441003407

Rapid Melting Fuse Link 8A (8K)

441003432

Rapid Melting Fuse Link 12A (12K)

441003456

Rapid Melting Fuse Link 15A (15K)

441003468

Rapid Melting Fuse Link 25A (25K)

441003481

Rapid Melting Fuse Link 40A (40K)

441003500

Slow Melting Fuse Link 10A (10T)

441003237

Slow Melting Fuse Link 15A (15T)

441003249

Slow Melting Fuse Link 20A (20T)

441003250

Slow Melting Fuse Link 25A (25T)

441003262

Slow Melting Fuse Link 30A (30T)

441003274

Slow Melting Fuse Link 40A (40T)

441003286

Slow Melting Fuse Link 65A (65T)

441003316

Slow Melting Fuse Link 100A (100T)

441003330

OFFICE

  • 13 Str Nikitara, Chalandri P.C. 15123

  • +30 210 6824538

  • +30 210 6824661

  • +30 210 6826256

PLANT

  • 1st Industrial Area of Volos, P.C. 38500

  • +30 24210 95102

  • +30 24210 95124

  • +30 24210 95403

CUSTOMER SERVICE

  • This email address is being protected from spambots. You need JavaScript enabled to view it.

  • This email address is being protected from spambots. You need JavaScript enabled to view it.

  • This email address is being protected from spambots. You need JavaScript enabled to view it.

ΓΕΜΗ 050676344000
Design & development by Web Intelligence